Quick FAQ....

I have a standpipe system with two risers. The original design indicates a total flow of 750 gpm (2839 Lpm). Am I required to flow this much water for the five year flow test?

No. When conducting the five year flow test, one riser is tested at a time. Therefore, the flow should be a total of 500 gpm (1892 Lpm), 250 gpm (946 lpm) for each of the two topmost outlets.